Cisco Switching/Routing :: 6513 Power Showing Wrong Wattage?
Oct 26, 2011
I just upgraded my power supply's from 2500Watts to 4000watts, however the show power still shows 2500watts.how do i make the 6513 recongize the change? I do have 250volts at 30 amps connected to each power supply.
system power redundancy mode = redundant
system power total = 2331.00 Watts (55.50 Amps @ 42V)
system power used = 1741.74 Watts (41.47 Amps @ 42V)
system power available = 589.26 Watts (14.03 Amps @ 42V)
[code]...
View 1 Replies
ADVERTISEMENT
May 14, 2012
I have 6500 core switch with 2500W power supply, and I want to install a second power supply with 3000W ? is this applicable ? if yes, is there a specific configuration that must be done ?
View 4 Replies
View Related
Apr 28, 2012
We have Communication Media Module (WS-SVC-CMM) mounted on 6513 switch. It went down twice and we brought it up by applying "power enable module".
View 4 Replies
View Related
Feb 26, 2012
I have 2 6513's between floors that have a port channel between them using 2 10 gig interfaces on 6704 cardsThis weekend I lost the port channel for about 4 mins and then it came back up. Unfort at the time I had logging turned off so was unable to get any info as to why. But I turned on debugging that eve and this morn it happened again.
Looks like Mod 9 is being power recycled, 6704 is about a year old and had been running for a month or so without issue.The only thing I have upgraded in the last few weeks was I put in a pair of 6000w supplies..But I am not having any other issuesother than mod 9. In hind sight a better design would be to spread this port channel across 10 gig cards. I'll work on that next.
2w2d: %OIR-SP-3-PWRCYCLE: Card in module 9, is being power-cycled 'Off (Module Reset due to exception or user request)'2w2d: %C6KPWR-SP-4-DISABLED: power to module in slot 9 set Off (Module Reset due to exception or user request)*Mar 1 00:00:02.331: DaughterBoard (Centralized Forwarding Card)
[Code].....
View 3 Replies
View Related
Apr 7, 2012
After a power problem at our data centre we find Module 11 of our Cisco 6513 Core Switch in PWR Down state.Show Module 11 returns: Status: PWRDownShow Power Status Module 11 returns: OperStatus Off (Module Reset due to an exception or user request).The command:
Power enable Module 11 was issued and returned the following: %PM_SCP-SP-1-LCP_FW_ERR: System resetting module 11 to recover from error: Linecard received system exception. Errcode = 2509000001.%OIR-SP-3-PWRCYCLE: Card in module 11 is being powercycled Öff (Module reset due to exception or user request%C6KPWR-SP-4-DISABLED: Power to module in slot 11 set off (Module Reset due to exception or user request),We have restarted the switch twice. The module is currently not passing traffic causing downtime to services.
View 6 Replies
View Related
Mar 6, 2013
I understand that 8700W enhanced AC power supply is Compatible with 6-, 9-, and 13- slot chassis
Based on 8700W Enhanced PS datasheet, it can be installed into existing Cisco Catalyst 6500 Series Switch chassis: both E- and non-E series Cisco Catalyst 6500 Series Switch chassis.
Can we use 8700W enhanced AC power supply with 6513 externally / internally (within one of the chassis slots like 6513-E ?
View 1 Replies
View Related
Oct 29, 2012
we have a chassis 6513-E and a module WS-X6748-GE-TX, I'd like to know if could I put this module in any slot, since the documentation from Cisco says that any slot from a chassis 6500-E Series can support this module. And then in the documentation of WS-X6748-GE-TX says that this module is not compatible in the slots 1-8 of the 6513 chassis, only from 9th to 13th slots, in those slots from the 6513-E we already have 4x WS-X6748-GE-TX, and we'd like to know if could we put the module in the rest of the slots. The 6513, and 6513-E is kind of confusing.
View 4 Replies
View Related
Jun 20, 2012
I have an ACS Server 5.1 which is used to authenticate my cisco and non-cisco devices. however when I take report on my authentications, the time shown in the report is wrong. However, when I take my mouse pointer to the report , the correct time is highlighted.
View 4 Replies
View Related
Sep 30, 2012
I have just connected a Cisco 2600 series router with a rolled over cable one port ( RJ-45 connector) in my console port and serial port in my PC COM1 port. Now when i open tera term and want to type something, the router is showing stange language.
View 13 Replies
View Related
Jun 9, 2013
I am receiving the following error on 3750 stack switches. have already verified the power status and found ok.
IOS used: Cisco IOS Software, C3750E Software (C3750E-UNIVERSALK9-M), Version 12.2(55)SE3, RELEASE SOFTWARE (fc1)
211540: Jun 10 10:45:17.935 UTC: %PLATFORM_STACKPOWER-4-UNBALANCED_PS: Switch 4's power stack has unbalanced power supplies
211541: Jun 10 10:46:18.045 UTC: %PLATFORM_STACKPOWER-4-UNBALANCED_PS:
[Code]....
View 1 Replies
View Related
Sep 4, 2012
After stacking two 3750X switches, with four equal power-supply's, with StackWise and PowerStack , still got the next message every few hours %PLATFORM_ENV-1-FRU_PS_ACCESS: FRU Power Supply is not responding (gn4m-rt1p08-04-2)( note that the message revers to the second switch in the stack ) although the stackwise and powerstack on the switches is oke and are working correctly. !
Config : Stack-power in power-sharing mode/strict With CLI on the switch : All the power supply's and stack-power details, prio look OK.
Only: LMS prime /inventory/cisco-view/configure/power supply status result : some power supply's are marked as disabled.with the command > power supply 2 slot a off/on I manage to get the status back to "normal", but after a few hours some power supply's are again marked as "disabled".
Looks like SNMP en IOS difference from opinion.
Hardware
WS-C3750X-24S-S
C3KX-PWR-350WAC
Software
15.0(2)SE
C3750E-UNIVERSALK9-M
View 5 Replies
View Related
Apr 14, 2013
We have two switches of the same model (WS-C3560-48PS-S) that are not providing PoE. I'm trying to remotely determine what the cause of the issue is.
Here is some output.
Hostname#show power inlineAvailable:0.0(w) Used:0.0(w) Remaining:0.0(w)
Interface Admin Oper Power Device Class Max (Watts)--------- ------ ---------- ------- ------------------- ----- ----Fa0/1 auto off 0.0 n/a n/a 15.4Fa0/2 auto off 0.0 n/a n/a 15.4Fa0/3 auto off 0.0 n/a n/a 15.4Fa0/4 auto off 0.0 n/a n/a 15.4Fa0/5 auto off 0.0 n/a n/a 15.4Fa0/6 auto off 0.0 n/a n/a 15.4Fa0/7 auto off 0.0 n/a n/a 15.4Fa0/8 auto off 0.0 n/a n/a 15.4Fa0/9 auto off 0.0 n/a n/a 15.4Fa0/10 auto off 0.0 n/a n/a 15.4(code)
View 1 Replies
View Related
Feb 28, 2011
I have a 6500 chassis with 2 power supplies. At the moment I am using the default configuration:
power-redudancy mode redundant
The problem is that an inserted module is in "power deny" state due too insufficient power.
I know, that It's not a good idea to change into combined mode (loss of redundancy), but my customers requested this anyway.
So I will change to combined mode. So here's the 1 million dollar question: "Which modules will go into power deny, if one of my power supplies fails?"
The 6500 config guide states:
"Power supply is removed withredundancy disabled
• System log and syslog messages are generated.
• System power is decreased to the power capability of one supply.
• If there is not enough power for all previously powered-up modules, some modulesare powered down and marked as power-deny in the show power oper state field."
Well, do you know if there's any way to configure some kind of priority? E.g. I definetly don't want by 10Gig Module or WiSM module to be in power deny. Can i statically make sure, those module will be powered on for sure? Like: "power enable module slot_number" How is this calculated? Or is random?
View 3 Replies
View Related
Apr 4, 2012
In a stand alone 3750x switch configuration, can the secondary power supply only act as a redundant power supply (active/standby), or can it become a "pool" of power similar to power sharing mode for StackPower (somewhat active/active)? I understand there is no stack involved here but I'm curious if this functionality is possible.
View 1 Replies
View Related
Jan 31, 2012
Well I have been back and forth on this a while now...I have a 6513E chassis that is getting prepped for prod. I am currently testing sso functionality and I can only get it to work using the following images on both Sup Cards.
s72033-adventerprise_wan-mz.122-33.SXI5.bin
If I try any other image, smaller or bigger in size...it forces my Sup card in mod 8 to recycle " proxy request from peer ". I have tried K9 images and non K9 images. Here is an output from sh redundancy.
Redundant System Information : Available system up time = 4 minutes Switch overs system experienced = 0 Standby failures = 0 Last switchover reason = none [code]...
View 2 Replies
View Related
Jul 31, 2012
I have a new 6513 with 2 sup32's with IOS. This chassis will replace a working 6513 with 2 sup2's with CatOS.I need to pull the running config from the CatOS chassis and make it work on the IOS chassis. i can do this manually but was wondering if there are any trade secrets on doing this.
View 3 Replies
View Related
Nov 21, 2011
I am replacing a faulty sup720 on a 6513. It s the backup/hot not the active sup. It has the same IOS on it. Is it correct that all I need to do is remove the faulty and replace it with the new sup and do a wr mem? Fromwat I have read their should be no down time all connectivity should remain stable?
View 6 Replies
View Related
Aug 9, 2012
I have a 6513 with redundant sup 720-3B's that I cannot get onto. In short, one of the power supplies failed, it still passes traffic but I can't console or ssh to the box. Other than the two sup 720's, I have a 4 port 10gig card, a 16 port GBIC Card and an IDS module. I have tried removing the 10Gig, IDS and one of the sup's but still don't get anything on the console. I have rebooted the entire chassis and don't get anything on my console while booting. I have tried changing the speed of my terminal to every setting available incase someone has changed it at some stage but to no avail. I have tried swapping sup's, using only one at a time in the chassis but not getting anything. Is there anything else I can try to get onto this chassis? The power supply is a 3000w with a 32amp input. The failed power supply had tripped a switch, when i brought it back up, the power supply came out but the output failed LED is on. My #questions are, is there anything else I can do to try get onto the console, and is the power supply goosed when the RED LED is lit? I have reseated the power supply also but the same result.
View 2 Replies
View Related
Apr 18, 2013
Are there any EOL notices out for the Catalyst 6513, 6509 etc E chassis? I cant find anything on the internet for the E variant, so assume this hasn't had a notice published yet.
View 2 Replies
View Related
Mar 10, 2013
My question is regarding VSS configuration on Cisco 6513 switches. My understanding is that the hardware and software configuration on the devices must be exactly the same for the VSS to function correctly. Do the Bootstrap versions also have to be identical?
The production switch is running Bootstrap Version 12.2(17r)SX5, while the new switch is running Bootstrap Version 12.2(17r)SX7.
View 3 Replies
View Related
May 16, 2012
I was working on adding a Cisco 6513 to TACACS but ran into trouble. While I work on the issue offline (recreate and test another switch), I wanted to place this switch on radius temporarily.
For some reason i cant undo/delete the AAA commands in order to point to my radius server. Below was done via console: [code]
I disabled my telemetry port on the Cisco 6513 as a precaution. The IOS im using is "s72033-advipservicesk9_wan-mz.122-33.SXI5.bin".how to remove the AAA authentication statement. Hope its not intrusive cause i have a customer on the box.
View 8 Replies
View Related
Aug 24, 2012
i have a cisco Netowtk Analysis module installed on a 6513 core switch which is NAM-1, the version on the NAM is 5.1 and we need to upgrade to the latest version which is 5.1(2)
View 1 Replies
View Related
Feb 27, 2012
I currently have a wired router (Cisco RV042), a wireless router (Cisco WRT110), and a switch for my network. I have the RV042 on a 192.168.5.1 subnet, and that is where my server and other local resources are. I wanted to add wireless for guests, but do not want the guests to have access to local resources, so I plugged the wireless router into RV042 and configured it for a 192.168.1.1 subnet. I can get internet access, but when I connect with a laptop to the wireless router, I end up being assigned an IP in the 5.1 subnet. I set up the VLAN setting in the RV042 for the correct port, but for some reason I am still being assigned the wrong IP, and I can hit local resources on the wireless.
View 1 Replies
View Related
Jul 12, 2012
I have a need to capture some traffic but my core 6513's are already using the limit of 2 span sessions. I can't edit any of the sessions either because I want to source traffic from vlans and you can only do one or the other. Is using a VACL with 'switchport capture' on the destination interface an option ? E.g. I want to source traffic from vlan 10,20,30,40 and send the all to interface Gi10/10 ? Is there any caveats ? I dont need to be too granular with the ACL's but just capture all traffic in those vlans.
View 2 Replies
View Related
Mar 20, 2013
Need your expert input in sorting out the below problem.I have a cisco 6513 switch which is going into SP mode after a reboot whci i have done during BCP activity in my organization.Below are the log for your reference.
Code...
View 1 Replies
View Related
May 9, 2012
i have a Cisco 6513 it is used one, i have tryed to boot it but it did not work, it alwayes go to rommon mode and i am not able to know what is the issue,
when it boot i get the below outpot from the switch.
System Bootstrap, Version 8.1(3)
Copyright (c) 1994-2004 by cisco Systems, Inc.
Testing lower main memory - data equals address
[Code].....
View 3 Replies
View Related
Jun 4, 2012
I am getting conflicting info about this, and need to get confirmations.Is the older 6513 (non E) model compatible with WS-X6407-10GE blade?The switch we're getting this for have WS-SUP720-3B, 6000W power supply, and WS-C6K-13SLT-FAN2.From what I read they are compatible if entered in slot 9-13, but I also heard that 10GE modules are not compatible with the non E chassis.
View 1 Replies
View Related
Feb 24, 2012
We have 2 6513's that are linked via 2 10 gig interfaces, using an LACP channel.I received an alert this aft stating that the far 6513 was unreachable and the port channel int PO3 had gone down, the 2 10 gig interfaces had also gone down on either side. 5 mins later PO3 had resestablished itself and has been fine since. [code]
View 4 Replies
View Related
Jul 11, 2011
We have a pair of 6513s and upgraded the IOS version to 12.2(33)SXI4a. After the upgrade we noticed VTP Pruning was disabled: [code] Is there any effect to production we need to to consider when re-enabling? (In other words, do we need to wait until a maintenance window to enable?)Also, we are using VTP v2 (and v1...) on our VTP Client 3560 access switches.
View 2 Replies
View Related
Feb 25, 2012
We have a Cisco 6513 Switch. During some parts of the day it is having large amounts of transmit discards on a certain interface because of the amount of data we are pushing. We have determined it is a link problem and not a problem with the switch. The link cannot handle the amount of packets the switch is pushing out. I was wondering if there is a way to create a buffer or a way to regulate the maximum amount of packets that can leave that interface without losing any packets?
View 5 Replies
View Related
May 8, 2013
I have just buy a 10G card for Cat 6513, these are information: PDCMSFC-1>sh module
Mod Ports Card Type Model Serial No.
--- ----- -------------------------------------- ------------------ -----------
2 16 SFM-capable 16 port 1000mb GBIC WS-X6516A-GBIC SAL08373Z37
7 2 Supervisor Engine 720 (Active) WS-SUP720-BASE SAD08330322
Mod Sub-Module Model Serial Hw Status
--- --------------------------- ------------------ ------------ ------- -------
7 Policy Feature Card 3 WS-F6K-PFC3A SAD083207AL 2.4 Ok
7 MSFC3 Daughterboard WS-SUP720 SAD0832037Y 2.3 Ok
About card: WS-X6716-10G-3C
When I install this card on Cat 6513, has a message: " fan tray no support"
View 5 Replies
View Related
Aug 1, 2007
I am running a network comprising of Catalyst 6513's with SUP7203B's. at present we have 800 VLAN's as we make use of a VLAN per access layer switch model.
I know have a problem that as soon as I enable multicast routing my SUP720's CPU runs at 100% and the system goes into a slowdown.where I can find information on the scalability of Multicast?
View 15 Replies
View Related
Mar 29, 2012
We have a 6513 with about 8 switches in it. I installed a Intel Pro PT NIC in a Dell PE2850 and setup the Team setting which created a bridge in the network connections.
10 minutes later, every server connected on that 'blade' went down and rebooted.
This happened once before to another tech here (I didn't know at the time it would do this but after he saw it he pointed it out)
View 2 Replies